Power Plant Equipment

Western Michigan University

Robert M. Beam Power Plant

 

Steam generating equipment
 

(All units operate at 200 psig, 480°F) 
 

UnitYearManufacturerCapacity(lb/hr)
HRSG 71997ERI-Nebraska65,000
HRSG 81997ERI-Nebraska65,000
Boiler 92004ERI-Nebraska65,000
Boiler 102009ERI-Nebraska65,000

Total steam capacity: 260,000 lb/hr.

Firm steam capacity (largest unit off line): 195,500 lb/hr.

Current peak steam demand: 145,000 lb/hr.

Historic peak steam demand: 290,000 lb/hr.

 

Electrical generating equipment

UnitYearManufacturerCapacity (kilowatts)
Turbine 72024Siemens SGT-AO5 HE5,000
Turbine 82022Siemens SGT-AO5 HE5,000
Steam Turbine1998Elliot900
Engine generator1999Caterpillar - 3516770
Peaking generator #92021Caterpillar - 3250H2,450
Peaking generator #102021Caterpillar - 3520H2,450

Total generating capacity: 16,570 kilowatts.

Average peak electric demand: 15,000 kilowatts.